This refrigerant has been prepared by mxing R32 +R125 + R143a + R134a in their mass percentages of 15 + 25 + 10 + 50 respectively. It belongs to HFC group of refrigerants. Its ODP is zero and GWP is 2000. It is neither toxic nor flammable. Therefore it comes under the safety class of Al. Its boiling point at atmospheric pressure is —42.7°C. It is mixable with polyolester oils. Therefore, after drawing out mineral or alkybenzene oil from the compressor, new polyolester (POE) oil should be charged. Mineral oil can also be used with R427A machine if an oil separator may be fitted with this machine. This refrigerant can be replaced in R22 refrigerant machine without making any special change.
Thursday, 11 January 2018
More Info
-
For retrofitting of R 22 machine with R 427 A proceed as under : 1. Start the machine charged with R 22 and note its temperatures and press...
-
Suction pressure . It is the absolute pressure of refrigerant at the inlet of a compressor. Discharge pressure. It is the absolute ...
-
1 Ton AC for 100 sq. foot room 1 Ton AC sufficient for 100 sq. To 120 sq. foot room 1.5 Ton AC sufficient 150 sq.foot 1.5 Ton A...
-
When the compressor and motor operate on the same shaft and are enclosed in a common casing, they are known as hermetic sealed compressors...
-
R-22 Standing pressure - 150 PSI Saction pressure - 60 TO 70 PSI Discha...

0 comments: